Reinforced Concrete - Floor Design (Beton Armat)

Proiect
8/10 (1 vot)
Domeniu: Construcții
Conține 5 fișiere: doc, dwg, bak
Pagini : 35 în total
Cuvinte : 4225
Mărime: 912.23KB (arhivat)
Publicat de: Aurelia Dragu
Puncte necesare: 10

Extras din proiect

CHAPTER I

BEAM AND GIRDER FLOOR

1.1. Data and specifications

A concrete floor slab type beam and girder is considered as a part of a building (Fig. 1.1), with two transversal spans: L = (9+0.1*n) m= 9.9 m

and longitudinal spans l = (6+0.1*n) m= 6.9 m

The resistant structure is realized of columns and girders, that are part of the floor.

Fig. 1.1

The floor is realized of o monolith slab that support on beams that transmit the load to girders (Fig. 1.1).

The ratio λ = is considered bigger than 2, the slab being reinforced on one direction: .

Concrete quality is chosen function the exposure class of the building in environment conditions. The design building is a textile production hall and there is not excessive humidity. According to Table I.1 and Fig. I.2a, Appendix I, the construction is included in class XC1 without corrosion risk or chemical attack. For this class the minimum concrete grade is C20/25.

The floor will have a minimum resistance to fire of 60 minutes (R60).

For concrete C20/25 the design strength in compression, using relation 2.11 and Table 2.1:

N/mm2

Tensile strength is obtained with the relation:

N/mm2

N/mm2

Steel reinforcement type S500 and welded mesh type STNB is used for the slab and beams.

• For S500 N/mm2

N/mm2

• For STNB (for d≤ 7.1 mm) N/mm2

The finish is realized of mosaic (30 mm depth) on a layer of cement plaster of 30 mm depth.

The service load is: = 5000 N/m2.

1.2. Design of Slab

1.2.1. Preliminary sizing of the slab

Flexural design will ordinarily consist in selecting a slab depth which will permit to use of an economical low steel ratio and which will not allow unsightly or damaging deflections.

For slabs elastically fixed on perimeter, the rigidity condition is:

hp ≥ a, where a is the opening parallel with the short side, a = 2.25 m.

hp = = 64.3 mm

And the minimum depth from technological condition to monolith slab, is 50 mm, the depth from the above conditions will be:

hp = 70 mm

From the fire condition the minimum depth is hp = 80 mm.

1.2.2. Widths for beams and girders

Fig. 1.2

From technological conditions the width of beams (bb) can be between 150 mm and 250 mm, and the width of girders (bg) and edge beams (beb) between 200 mm and 350 mm. From fire resistance condition b> 120 mm.

One chooses:

bg = 300 mm

beb = 300 mm

bb = 200 mm

Preview document

Reinforced Concrete - Floor Design (Beton Armat) - Pagina 1
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 2
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 3
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 4
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 5
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 6
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 7
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 8
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 9
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 10
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 11
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 12
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 13
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 14
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 15
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 16
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 17
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 18
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 19
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 20
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 21
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 22
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 23
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 24
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 25
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 26
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 27
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 28
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 29
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 30
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 31
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 32
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 33
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 34
Reinforced Concrete - Floor Design (Beton Armat) - Pagina 35

Conținut arhivă zip

  • grinda principala otilia.bak
  • grinda principala otilia.dwg
  • grinda secundara otilia.bak
  • grinda secundara otilia.dwg
  • Reinforced Concrete - Floor Design (Beton Armat).doc

Te-ar putea interesa și

Casă de locuit

TECHNICAL REPORT According to the design theme, “Dwelling P +2E", and the requirements related to location, nature of the soil, the climate,...

Ai nevoie de altceva?